HPH Series 60-120kVA

Best-in-class power protection with minimum power and cost effciency

Features and Benefits

  • Best-in-Class Power Performance and Efficiency
    • Fully rated power (kVA=kW) for maximum power availability
    • Leading AC-AC efficiency up to 96% saves energy costs
    • Low harmonic pollution (iTHD < 3%) and high input power factor (> 0.99) reduce upstream investment costs
  • Assured Reliability
    • Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life
    • DSP based technology enables reduction in the number of electronic components to lower failure rate
    • Redundant auxiliary power and static switch control circuit* design prevents single point of failure (* Applied for models HPH-100/120K)
    • Watch-dog design of dual auxiliary power circuit to eliminate single-point failure to ensure reliability
    • Built-in manual bypass ensures continuous power to the load even if the UPS is under maintenance
  • Greater Flexibility
    • A wide choice of configurations, such as N+X redundancy and hot stand-by
    • Adjustable charging current and charging voltage meet different battery configuration requirements
    • Flexible battery configuration optimizes battery investment
  • Superior Serviceability and Management
    • Swappable interior architecture and front access servicing enables quick and easy maintenance
    • Multi-connectivity interface supports remote UPS monitoring and management

Available to Order

Models

Overview

How to Buy

Click “WhatsApp Us” or “Get a Quote” above to buy Delta DPH Series UPS, 50 – 300/500/600 kVA​ from APulsar Technologies, Delta Official Distributor.

Introduction

Behind every great design there is an answer. Delta’s true online double-conversion Ultron HPH Series is the solution for small and medium data centers and mission critical applications requiring highly reliable power protection and unbeatable energy efficiency.

The innovation behind the Ultron HPH Series UPS design incorporates low iTHD (< 3%), 96% AC-AC and 99% ECO mode energy efficiency for increased Total Cost of Ownership (TCO) savings. Fully rated power (kVa=kW) without de-rating, the Ultron UPS offers leading AC-AC efficiency without sacrificing any available power requirements. Increased availability is further augmented through Ultron HPH watch-dog design.

Quite simply, the HPH Series UPS from Delta is a best-in-class (three phase 60/80/100/120 kVA UPS) power protection system that combines maximum available power, unsurpassed energy efficiency, and superior power performance with a significant advantage: TCO savings. HPH is an ideal choice for datacenters as well as for industries involved in factory equipment, communication systems, computer network systems, medical systems, monitoring systems and more.

Specifications

Power Rating

• HPH-60K: 60 kVA/kW
• HPH-80K: 80 kVA/kW
• HPH-100K: 100 kVA/kW
• HPH-120K: 120 kVA/kW

  • Nominal Voltage: 380/400/415 Vac, 3P4W+PE
  • Voltage Range
    332-477 Vac (full load)
    228-332 Vac (with derating from 63-100% load)
  • Frequency: 40-70 Hz
  • Total Harmonic Distortion (THDi): < 3%
  • Power Factor: > 0.99 (full load)
  • Short Circuit Withstand Rating
    • HPH-60K: 15 A
    • HPH-80K/100K/120K: 22 A
  • Voltage: 380/400/415 Vac, 3P4W+PE
  • Voltage Regulation: ± 1%
  • Frequency: 50/60 ± 0.05 Hz
  • Total Harmonic Distortion (THDv): ≤ 2% (Linear Load)
  • Power Factor: 1.0
  • Overload Capability
    ≤ 125%: 10 mins; 126-150%: 1 min; > 150%: 1 sec
  • Current Crest Ratio: 3:1
  • Online Mode: > 96%
  • ECO Mode: Up to 99%
  • Battery Type: VRLA
  • Nominal Voltage: ±240 Vdc
  • Quantity: 32-46 pcs(1)
  • Charge Current
    • HPH-60K: 10 A
    • HPHH-80K: 15 A
    • HPH-100K/120K: 20 A
  • Max. Charger Current with Optional Charger Board
    • HPH-60/80K: 20 A
    • HPH-100/120K: 40 A
  • Display: LCD Screen with LED Indicators
  • Port: Smart slot x1, Mini slot x1, Parallel port x2, RS-232 x1, Charger detection port x1, Input dry contact x2, Output dry contact x6, USB x1, REPO port x1, External battery temperature sensing port x2
  • Emergency Power Off: Yes
  • Dimensions (W x D x H)
    • HPHH-60K/80K: 520 x 800 x 1175 mm
    • HPH-100K/120K: 520 x 800 x 1760 mm
  • Net Weight
    • HPH-60K: 186.5 kg
    • HPH-80K: 191 kg
    • HPH-100K/120K: 312 kg
  • Packing Dimensions (W x D x H)
    • HPH-60K/80K: 685 x 1003 x 1337 mm
    • HPH-100K/120K: 720 x 994 x 1952 mm
  • Packing Weight
    • HPH-60K: 220.5 kg
    • HPH-80K: 225 kg
    • HPH-100K/120K: 388 kg
  1. Operating Temperature: 0 to 45˚C(2)
  2. Humidity: 5-95 % (non-condensing)
  3. Altitude: 0-1,000 m (without derating)
  4. Storage Temperature: -20 to +50 °C
  5. Ingress Protection: IP20
  • Safety: CE
  • EMC: IEC 62040-2
  • Performance: IEC 62040-3
  • Sustainability: RoHS, REACH
  • Backfeed Protection: Standard
  • Cold Start Function: Standard
  • Synchronized Multiple Bus (SMB): Standard
  • Advanced Power Walk-in for Generator: Option
  • Dual Input: Option