MGate 4101-MB-PBS Series

Features and Benefits

  • Protocol conversion between Modbus and PROFIBUS
  • Supports PROFIBUS DP V0 slave
  • Supports Modbus RTU/ASCII master and slave
  • Windows utilities with innovative QuickLink function for automatic configuration within minutes
  • Status monitoring and fault protection for easy maintenance
  • Embedded traffic monitoring/diagnostic information for easy troubleshooting
  • Supports redundant dual DC power inputs and 1 relay output
  • -40 to 75°C wide operating temperature models available
  •  Serial port with 2 kV isolation protection (for “-I” models)

Models

Overview

Introduction

The MGate 4101-MB-PBS gateway provides a communication portal between PROFIBUS PLCs (e.g., Siemens S7-400 and S7-300 PLCs) and Modbus devices. With the QuickLink feature, I/O mapping can be accomplished within a matter of minutes. All models are protected with a rugged metallic casing, are DIN-rail mountable, and offer optional built-in optical isolation.

QuickLink and Windows Utilities for Easy Setup and Traffic Monitoring

The QuickLink windows utility uses a serial console port to connect to the MGate 4101-MB-PBS and makes configuration and operation as easy as possible. QuickLink can finish the configuration in just a few minutes by passively detecting Modbus requests with the AutoLearning function, and performs error-free I/O mapping with the AutoMapping feature. QuickLink drastically reduces Modbus-to-PROFIBUS integration time when compared to conventional I/O mapping, which can easily require days to complete. Additionally, embedded monitoring tools can maintain logs of Modbus communication packets and assist in troubleshooting.

Redundant Power Inputs

The MGate 4101-MB-PBS has dual power inputs for greater reliability. The power inputs allow simultaneous connection to 2 live DC power sources, so that continuous operation is provided even if one power source fails. The higher level of reliability makes these advanced Modbus-to-PROFIBUS gateways ideal for demanding industrial applications.

Warning by Relay Output

A relay output is provided for the power input status. The relay output gives maintenance engineers an additional tool for troubleshooting and maintenance.

Specifications

Serial Interface

Console Port

  • RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1)

No. of Ports

  • 1

Connector

  • DB9 male

Serial Standards

  • RS-232/422/485

Baudrate

  • 50 bps to 921.6 kbps

Data Bits

  • 7, 8

Parity

  • None, Even, Odd, Space, Mark

Stop Bits

  • 1, 2

Flow Control

  • DTR/DSR
  • RTS/CTS

RS-485 Data Direction Control

  • Automatic Data Direction Control (ADDC)

Pull High/Low Resistor for RS-485

  • 1 kilo-ohm, 150 kilo-ohms

Terminator for RS-485

  • 120 ohms

Isolation

  • 2 kV (I models)

RS-232

  • TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND

RS-422

  • Tx+, Tx-, Rx+, Rx-, GND

RS-485-2w

  • Data+, Data-, GND

RS-485-4w

  • Tx+, Tx-, Rx+, Rx-, GND

Configuration Options

  • MGate Manager

Industrial Protocols

  • Modbus RTU/ASCII Master
  • Modbus RTU/ASCII Slave
  • PROFIBUS DP-V0 Slave

Mode

  • Master, Slave

Functions Supported

  • 1, 2, 3, 4, 5, 6, 15, 16, 23

Max. No. of Commands

  • 100

Input Data Size

  • 7744 bytes

Output Data Size

  • 7744 bytes

Industrial Protocols

  • PROFIBUS DP

No. of Ports

  • 1

Connector

  • DB9 female

Baudrate

  • 9600 bps to 12 Mbps

Isolation

  • 2 kV (built-in)

Signals

  • PROFIBUS D+, PROFIBUS D-, RTS, Signal Common, 5V

Rotary Switch

  • PROFIBUS addresses 0-99 (addresses 100-125 supported through software configuration)

Mode

  • DP-V0 Slave

Max. No. of Master Connections

  •  1

Max. No. of PROFIBUS I/O Modules

  • 24 per page

Max. No. of PROFIBUS Pages

  • 32

Input Data Size

  • 7744 bytes

Output Data Size

  • 7744 bytes

Input Voltage

  • 12 to 48 VDC

Input Current

  • 275 mA @ 12 VDC

Power Connector

  • Screw-fastened Euroblock terminal

Contact Current Rating

  • Resistive load: 1 A @ 24 VDC

Housing

  • Metal

Dimensions

  • 36 x 105 x 140 mm (1.42 x 4.14 x 5.51 in)

Weight

  • 500 g (1.10 lb)

IP Rating

  • IP30
    Note: It is recommended to attach the M3x3mm Nylok screws at the rear side

Operating Temperature

  • MGate 4101I-MB-PBS: 0 to 60°C (32 to 140°F)
  • MGate 4101I-MB-PBS-T: -40 to 75°C (-40 to 167°F)
  • MGate 4101-MB-PBS: 0 to 60°C (32 to 140°F)
  • MGate 4101-MB-PBS-T: -40 to 75°C (-40 to 167°F)

Storage Temperature (package included)

  • -40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

  • 5 to 95% (non-condensing)

EMC

  • EN 55032/35

EMI

  • CISPR 32, FCC Part 15B Class A

EMS

  • IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
  • IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
  • IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
  • IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV
  • IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m
  • IEC 61000-4-8 PFMF

Safety

  • IEC 60950-1
  • UL 60950-1
  • IEC 62368-1
  • UL 62368-1

Hazardous Locations

  • ATEX
  • Class I Division 2
  • IECEx

Freefall

  • IEC 60068-2-32

Shock

  • IEC 60068-2-27

Vibration

  • IEC 60068-2-6
  • IEC 60068-2-64

 

Time

  • MGate 4101-MB-PBS models: 1,537,948 hrs
  • MGate 4101I-MB-PBS models: 1,315,666 hrs

Standards

  • Telcordia SR332

Warranty Period

  • 5 years
  • MGate 4101-MB-PBS
  • MGate 4101I-MB-PBS
  • MGate 4101-MB-PBS-T
  • MGate 4101I-MB-PBS-T