Delta MX Series 1.1/2/3 kVA

Features and Benefits

  • Availability
    • Microprocessor-based line interactive design for fast response to power disturbances
    • Programmable load bank disconnects non-critical loads when a blackout occurs and reserves more battery power for critical loads
    • Automatic voltage regulator (AVR) delivers stable output voltage during brownouts or over-voltages
    • Wide input voltage range allows the UPS to work in harsh electrical environments
    • Hot-swappable battery design to protect equipment during battery replacement
  • Flexibility
    • Supports both rack and tower installation
    • Excellent management through a user-friendly graphical and easy-shift LCD display to suit different installation format
    • Supports multiple communication interfaces, including USB port, RS-232, Mini Slot, Surge Protection, REPO for enhanced monitoring and manageability
  • Low Total Cost of Ownership
    • Output power factor is up to 0.9 to provide more real power to critical loads
    • High efficiency normal mode reach at 98% and 98.5% for 3kVA
    • Wide input range and protection against over voltage prolongs battery life

Available to Order

Models

  • MX-1.1K
  • MX-2K
  • MX-3K

Overview

Introduction

The Amplon MX line-interactive UPS provides pure sine-wave quality compatibility for versatile applications and protect devices for small-and-medium businesses from power failure and voltage variations in small footprint. The Amplon MX series features enhanced output power factor 0.9, AVR Efficiency up to 96.5%, resulting in a greater power supply for critical loads at significantly less operating cost.

Specifications

Topology
  • Line interactive
  • Sinewave

MX-1.1K

  • 1.1 kVA
  • 0.99 kW

MX-2K

  • 2 kVA
  • 1.8 kW

MX-3K

  • 3 kVA
  • 2.7 kW

 

Nominal Voltage

  • 200/208/220/230(default)/240 Vac, 1P2W+PE

Voltage Range

  • 170-280 Vac(¹)

Frequency Range

  • 45-65 Hz

Plug Type(1)

MX-1.1K

  • IEC C14

MX-2K & MX-3K 

  • IEC C20

 

(1) 200 V: 150-234 Vac, 208 V: 156-243 Vac, 220 V: 162-268 Vac, 240 V: 177-290 Vac

Nominal Voltage

  • 200/208/220/230/240 Vac, 1P2W+PE

Voltage Regulation

  • ±1.5%

Frequency

  • 50/60 ± 1 Hz

Total Harmonic Distortion (THDv)

  • < 2% (linear load); < 5% (non-linear load)

Power Factor

  • 0.9

Connection

MX-1.1K & MX-2K

  • Programmable outlet IEC C13 x4,Non-programmable outlet IEC C13 x4

MX-3K

  • Programmable outlet IEC C13 x4,Non-programmable outlet IEC C13 x4. IEC C19 x1

Overload Capability

  • < 103%: continues; 103-120%: 5 mins; 120-150%: 10 secs

Current Crest Ratio

  • 3:1

Normal Mode

MX-1.1K

  • 98%

MX-2K

  • 98.3%

MX-3K

  • 98.5%

AVR Mode

MX-1.1K

  • 95.5%

MX-2K & MX-3K

  • 96.5%

Battery Type

  • VRLA

Nominal Voltage

  • 24 Vdc 48 Vdc 72 Vdc

Quantity

  • 2 pcs
  • 4 pcs
  • 6 pcs

Runtime

  • 100% Load 2.7 mins 3.4 mins 3.7 mins
  • 75% Load 5 mins 6.1 mins

Recharge Time

  • 4 hours to 90%

Display

  • LCD display with LED indicators

Port

  • USB, RS-232, Mini slot, REPO, Surge protection

Audible Alarm

  • Battery mode, Low battery, Battery missing/replacement, Overload, Fault, EPO enable, Over temperature

Emergency Power Off

  • Yes

Dimensions (W x D x H)

MX-1.1K

  • 438 x 410 x 88 mm

MX-2K

  • 438 x 510 x 88 mm

MX-3K

  • 438 x 630 x 88 mm

Net Weight

MX-1.1K

  • 14.1 kg

MX-2K

  • 21.3 kg

MX-3K

  • 32.1 kg

Packing Dimensions (W x D x H)

MX-1.1K

  • 500 x 560 x 180 mm

MX-2K

  • 565 x 700 x 200 mm

MX-3K

  • 600 x 760 x 200 mm

Packing Weight

MX-1.1K

  • 16.1 kg

MX-2K

  • 29.7 kg

MX-3K

  • 35.3 kg

Operating Temperature

  • 0 to 40°C (without derating)

Humidity

  • 20-90% (non-condensing)

Audible Noise

  • < 45 dBA

Altitude

  • 0-3000 m (derating 1%/100m from 1501-3000 m)

Storage Temperature

  • -20 to 50°C

 

 

Safety

  • CE, UKCA, TISI, RCM

Sustainability

  • RoHS, REACH