Delta DPH Series UPS, 50 – 300/500/600 kVA​

Features and Benefits

  • The industry’s leading power density per module at 50kW in 3U space, with the smallest footprint for 500kVA in a single rack and 600kVA in two racks
  • High AC-AC efficiency up to 96.5% and ECO mode up to 99% results in marked energy cost savings
  • Fully modularized design and hot-swappable key modules ensure Mean Time To Repair (MTTR) close to zero without downtime risk
  • Modular UPS grows with your business by parallel expansion up to 8 units for 4.8MVA of total power capacity
  • User-friendly 10” color touch screen enables easy local UPS management

Available to Order

Models

  • 300/500kVA
  • 600kVA
  • 300kVA
  • 500kVA
  • 600kVA

Overview

Introduction

In this IT intensive world with heavy data traffic driven by cloud, 4G/5G and media streaming applications, IT managers are facing the challenges of increasing rack power density and limited data center space. Delta’s innovative modular UPS technologies provide the answer to customers’ demands for high power density, high power performance, and ultimate availability. The brand-new Delta Modulon DPH series UPS 50-300/500/600 kVA achieves the industry’s leading power density of 50kW per module, offering the smallest footprint and best space utilization. The Modulon DPH Series UPS is the ideal modular power protection for MW data centers to achieve total cost of ownership (TCO) optimization.

Specifications

Power Rating

kVA

DPH-300K

  • 50-300

DPH-500K

  • 50-500*

DPH-600K

  • 50-600

kW

DPH-300K

  • 50-300

DPH-500K

  • 50-450

DPH-600K

  • 50-600

Power Module Rating

  • 50 kW

Power Module Quantity

DPH-300K

  • Up to 6 units

DPH-500K

  • Up to 9 units

DPH-600K

  • Up to 12 units

Nominal Voltage

  • 220/380 Vac; 230/400 Vac; 240/415 Vac (3-phase, 4-wire + G)

Voltage Range

  • 305-477 Vac (full load), 229-305 Vac (70~100% load)

Current Harmonic Distortion

  • < 3%**

Power Factor

  • > 0.99

Frequency Range

  • 40~70 Hz

Voltage

  • 220/380 Vac; 230/400 Vac; 240/415 Vac (3-phase, 4-wire + G)

Voltage Harmonic Distortion

  • ≤ 0.5% (linear load)

Voltage Regulation

  • ±1% (static)

Frequency

  • 50/60 Hz ± 0.05 Hz

Overload Capability

  • ≤ 125%: 10 minutes; ≤ 150%: 1 minute; >150%: 1 second
  • 10” color touch screen

Standard

  • RS232 x 1, Parallel port x 4, USB type A x 2, USB type B x 1, MODBUS x 1, Smart slot x 1, REPO x 1, EPO x 1, Input dry contact x 4, Output dry contact x 6, External battery temperature detection x 4, External switch/breaker status dry contact x 4, BMS (RJ45) x 1, Ethernet x 1

Optional

  • Relay I/O card, Battery cabinet temperature sensor cable

Safety

  • CE

AC-AC

  • Up to 96.5%

ECO Mode

  • 99%

Nominal Voltage

  • ±240 Vdc (default, ±180 Vdc to ±276 Vdc configurable)

Charge Voltage

  • ±272 Vdc (adjustable from 204 Vdc to 312 Vdc)

Protection of Battery Deep Discharge

  • Yes

Operating Temperature

  • 0~40ºC

Relative Humidity

  • 0~90% (non-condensing)

Audible Noise (at 1 meter)

DPH-300K

  • < 75 dB

DPH-500K

  • < 80 dB

DPH-600K

  • < 85 dB

IP Protection

  • IP20

Parallel Redundancy and Expansion

  • Module and system redundancy; Maximum 8 units

Emergency Power Off

  • Remote (default) and local (optional)

Battery Start

  • Yes

Dimensions (W x D x H)

  • 600 x 1100 x 2000 mm 1200 x 1100 x 2000 mm

Weight: UPS System (without power modules)

DPH-300K

  • 311 kg

DPH-500K

  • 317 kg

DPH-600K

  • 605 kg

Weight: 50 kW Power Module

  • 36 kg (optional)