Eaton 9SX Gen2 UPS

Features and Benefits

  • 5 to 11 kW power rating range
  • 97,2 % in the 11kW unit
  • Wide-bandgap technology

Models

9SX G2 5kVA

  • UPS (RT with rack kit): 9SX5KIRT3UG2
  • EBM (RT with rack kit): 9SXEBM180RT3UG2
  • HotSwap Maintenance Bypass: MBP6KIG2
  • 2m battery connection cable: EBMCBL180RT

9SX G2 6kVA

  • UPS (RT with rack kit): 9SX6KIRT3UG2
  • EBM (RT with rack kit): 9SXEBM180RT3UG2
  • HotSwap Maintenance Bypass: MBP6KIG2
  • 2m battery connection cable: EBMCBL180RT

9SX G2 8kVA

  • UPS (RT format): 9SX8KIG2
  • UPS (RT with rack kit): 9SX8KIRT4UG2
  • EBM (RT format): 9SXEBM240G2
  • EBM (RT with rack kit): 9SXEBM240RT3UG2
  • HotSwap Maintenance Bypass: MBP11KIG2
  • 2m battery connection cable: EBMCBL240RT
  • Rack Kit: 9RK

9SX G2 11kVA

  • UPS (RT format): 9SX11KIG2
  • UPS (RT with rack kit): 9SX11KIRT4UG2
  • EBM (RT format): 9SXEBM240G2
  • EBM (RT with rack kit): 9SXEBM240RT3UG2
  • HotSwap Maintenance Bypass: MBP11KIG2
  • 2m battery connection cable: EBMCBL240RT
  • Rack Kit: 9RK

Overview

How to Buy

Click “WhatsApp Us” or “Get a Quote” above to buy Eaton 9SX Gen2 UPS from APulsar Technologies, Eaton Authorised Direct Reseller.

Order online and enjoy fast delivery across Kuala Lumpur and the entire Malaysia.

Introduction

Eaton’s 9SX Gen2 UPS is a single-phase online UPS with ratings from 5 to 11kW. It delivers battery backup and power management for critical equipment in data centres, distributed IT, edge networks, network closets and server rooms.

This UPS helps you reduce your physical footprint (up to 11kW in 4U) and your energy bill (Energy-Star qualified) while it delivers 11% more power than its predecessor.

Leverage predictive machine learning to pinpoint battery replacement needs before you suffer disruption.

Eaton 9SX Gen2 is compatible with the cybersecured Gigabit Network Card, and Brightlayer Datacenter software suite.

 

Specifications

Power rating

5 kVa

  • 5kVA/5kW

6kVA

  • 6kVA/6kW

8kVA

  • 8kVA/8kW

11kVA

  • 11kVA/11kW

Technology

  • On-line double conversion with Power Factor Correction (PFC) system

Nominal voltage

  • 200/208/220/230/240V

Input voltage range

  • 176-276V without derating (100-276V with derating)

Output voltage / THDv

  • 200/208/220/230/240V +/- 1%; THDv <1%

Input frequency range / THDI

  • 40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 3%

Efficiency

  • 5 kVa, 6 kvA: Up to 96.7% in Online mode
  • 8 kVa, 11 kVA: Up to 97.2% in Online mode

Crest factor/short circuit current

  • 5 kVa, 6 kvA: 3:1 / 90A
  • 8 kVa: 3:1 / 120A
  • 11 kVa: 3:1 / 150A

Overload capacity

  • 102%-125%: 10min, 125%-150%: 30s, >150%: 0.5s

Input

  • 5 kVa, 6 kvA: Terminal block (up to 10 mm2)
  • 8 kVa, 11 kVA: Terminal block (up to 16mm2)

Outputs

  • 5 kVa, 6 kvA: Terminal block + 3 C19 + 8 C13 (2 controlled groups)
  • 8 kVa, 11 kVA: Terminal block + 4 C19 + 8 C13 (2 controlled groups)

Typical backup times:

Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc

5kVA/+1EBM/+4EBM

  • 1000W: 31/113/384
  • 2000W: 13/52/185
  • 4000W: 5/22/86

6kVA/+1EBM/+4EBM

  • 1000W: 31/113/384
  • 2000W: 13/52/185
  • 4000W: 5/22/86
  • 6000W: 2.5/13/53

8kVA/+1EBM/+4EBM

  • 1000W: 65/145/410
  • 2000W: 25/65/185
  • 4000W: 10.5/27/89
  • 6000W: 5.5/16/56
  • 8000W: 3.5/10.5/39

11kVA/+1EBM/+4EBM

  • 1000W: 65/145/410
  • 2000W: 25/65/185
  • 4000W: 10.5/27/89
  • 6000W: 5.5/16/56
  • 8000W: 3.5/10.5/39
  • 10000W: 2/7.5/30

Battery management

  • ABM+ (Predictive battery life) & Temperature compensated charging method, Automatic battery test, deep discharge protection, automatic recognition of external battery units

Communication Ports

  • 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 mini terminal blocks (Dry contacts, 2 inputs, 2 outputs)

Communication Slot

  • 1 slot for Network-M3, INDGW-M2, INDRELAY-MS or Relay-MS

Operating temperature

  • 0 to 40°C continuous

Typical Noise level

Typical noise level (load level below 66% and ambiant temperature below 30°C)

  • 38db

Safety

  • IEC/EN 62040-1, UL 1778 & CSA 22.2

EMC, Performance

  • IEC/EN 62040 -2 , IEC/EN 62040-3

Approvals

  • CE, CB report (TUV), UL (except 9SXEBM240G2 & 9SXEBM240RT3UG2)

UPS

  • 5 kVa, 6 kvA: 440(19’’) x 130(3U) x 684 mm/43.1kg
  • 8 kVa, 11 kVA: 440(19’’) x 174(4U) x 725mm/78.8kg

EBM

  • 5 kVa, 6 kvA: 440(19’’) x 130(3U) x 636mm/65.7kg
  • 8 kVa, 11 kVA: 440(19’’) x 130(3U) x 670mm/62kg

2 years