ioPAC 6500 Series (65M) I/O Modules

Features and Benefits

  • Supports multiple IT/OT protocols for seamless communication between SCADA, Plant Information System, and cloud applications
  • Tool-free hardware installation and hot-swappable design , maximizing operation efficiency
  • Fully modular design for maximum deployment flexibility
  • Turbo Ring, Turbo Chain, and RSTP/STP for network redundancy
  • IINxpress IDE utility combines IEC 61131-3 programming, configuration, and protocol services to streamline workflow and reduce programming efforts
  • Developed according to IEC 62443-4-2 SL2 standards to ensure a secure foundation for critical applications

Models

  • 65M-1900-CT-T
  • 65M-3600-CT-T
  • 65M-3610-CT-T
  • 65M-2901-CT-T
  • 65M-4820-CT-T

Overview

How to Buy

Click “WhatsApp Us” or “Get a Quote” above to buy ioPAC 6500 Series (65M) I/O Modules from APulsar Technologies, MOXA official distributor.

Purchase walk-in from our office in Petaling Jaya, or order online and enjoy fast delivery across Kuala Lumpur and the entire Malaysia.

Introduction

The ioPAC 6500 Series is a new generation of Linux-based controllers featuring a built-in Layer-2 managed switch. Equipped with an Arm Cortex-A53 quad-core CPU, the ioPAC 6500 Series delivers robust performance.

6C Competencies

The ioPAC 6500 Series delivers the following competencies to your projects:

  • Control: Precision control of your equipment
  • Communication: Protocol support to connect to other devices and systems
  • Computing: Applications for computing and data processing
  • Connectivity: Versatile set of media interface supported by the ioPAC 6500 Series
  • Cloud: Cloud connectivity and cloud edge computing
  • Cybersecurity: Security features to protect the devices and data

Fully Modular Design

The ioPAC 6500 Series features a unique Lego-like mechanical design that allows for flexible deployment while minimizing installation efforts. The series can be divided into the components: Backplane modules, power modules, communication modules, CPU modules, I/O modules, and terminal-block modules.

IEC 61131-3 Automation Programming

IoPAC 6500 Series features IEC 61131-3 automation programming for flexibility in automation design and consistency in syntax and semantics, promoting interoperability between systems, thereby reducing development complexity in automation projects. Five languages are available: LD, FBD, SFC, IL, and ST, allowing automation professionals to choose the programming language that best suits their needs.

Specifications

Input/Output Interface

Digital Input Channels

  • 65M-1900-CT-T: 32

Digital Output Channels

  • 65M-2901-CT-T: 32

Analog Input Channels

  • 65M-3600-CT-T: 16 (current)
  • 65M-3610-CT-T: 16 (voltage)

Analog Output Channels

  • 65M-4820-CT-T: 8

Isolation

  • 65M-3600-CT-T/65M-3610-CT-T/65M-4820-CT-T:
    System: 3k VDC
    Signal: 1k VDC (between group for 1 min)
  • All other models:
    System: 3k VDC
    Signal: 3k VDC

I/O Type

  • Sink
    (Internal/external sensor supply for dry contact)

I/O Mode

  • DI or event counter
    (channels 1 to 8, group configurable by software)

Input Voltage

  • On: 11 to 30 VDC
  • Off: 0 to 5 VDC

Input Current (voltage on)

  • 2.35 mA ± 20% per channel

Counter Frequency

  • Square wave: 0 to 10 kHz

Digital Filtering Time Interval

  • Software configurable

Diagnostics

  • Input Wire-break Detection (current: 50 µA max., delay: 20 ms)
  • Internal Field Circuit Supply Detection (17.5 VDC, 16 to 19 VDC)

I/O Type

  • Source

I/O Mode

  • DO or pulse output
    (channel 1 to 8, group configurable by software)

Pulse Duration

  • 500 μs

Protection

  • Output Short-circuit Protection
  • Common Power Input Over-voltage Protection
  • Inductive Load Shutdown Voltage Protection

Diagnostics

  • Wire Break Detection (on state, output current < 3 mA)
  • Wire Break Detection (off state, output load impedance > 58 kilo-ohms)
  • Output Short-Circuit Detection (output current > 0.87 A, range: 0.64 to 1.2 A)
  • External Power Detection (17.5 VDC, 16 to 19 VDC)
  • Failsafe Configuration (hold last/failsafe state)

I/O Mode

  • 65M-3600-CT-T: Current
  • 65M-3610-CT-T: Voltage

I/O Type

  • Differential

Input Range

  • 65M-3600-CT-T:
    0 to 20 mA
    4 to 20 mA
  • 65M-3610-CT-T:
    0 to 10 V
    1 to 5 V

Overload Permitted on Inputs

  • 65M-3600-CT-T: ±30 mA
  • 65M-3610-CT-T: ±12 V

Measurement Resolution

  • 65M-3600-CT-T:
    2 μA (0 to 20 mA)
    1.6 μA (4 to 20 mA)
  • 65M-3610-CT-T:
    1 mV (0 to 10 V)
    0.4 mV (1 to 5 V)

Accuracy

  • ±0.1% FSR @ 25°C
  • ±0.3% FSR @ -40 to 75°C

Conversion Time

  • 100 ms

Rejection Ratio

  • Normal mode: > 60 dB @ 60 Hz (min.), conversion time: 100 ms
  • Common mode: > 90 dB @ 60 Hz (min.), conversion time: 100 ms

Input Impedance

  • 65M-3600-CT-T: 250 ohms
  • 65M-3610-CT-T: 1 mega-ohms

Diagnostics

  • 65M-3800-3810-CT-T:
    Input Underflow/Overflow Detection
  • 65M-3600-CT-T:
    Internal Loop Power Detection (17.5 VDA, 16 to 19 VDC)
    Input Short-circuit Detection
  • 65M-3600-CT-T (in 4 to 20 mA mode):
    Input Wire-break Detection (delay: 0.8 s)
  • 65M-3610-CT-T:
    Input Wire-break Detection (delay:1.6 s max)

I/O Mode

  • Voltage/Current

Output Range

  • 0 to 10 V
  • 1 to 5 V
  • 0 to 20 mA
  • 4 to 20 mA

Converter Resolution

  • 16-bit

Accuracy

  • ±0.1% FSR @ 25°C
  • ±0.3% FSR @ -40 to 75°C

Output Refresh Time

  • 16 ms

Output Impedance

  • Voltage mode:
    1 kilo-ohms (min.)
  • Current mode:
    750 ohms (max.)

Diagnostics

  • Output Short-circuit Detection (voltage)
  • Failsafe Configuration (hold last/failsafe state)
  • Output Wire-break Detection (current)

Connector

  • Screw-fastened terminal block

ID

  • 65M-TB-1900-CT-T: D1
  • 65M-TB-2901-CT-T: D2
  • 65M-TB-3600-CT-T: A1
  • 65M-TB-3610-CT-T: A2
  • 65M-TB-4820-CT-T: A5

Dimensions

  • 42.3 x 102.38 x 80.8 mm (1.67 x 4.03 x 3.18 in)

Weight

  • 164 g (0.36 lb)

System Power

  • 65M-1900-CT-T:
    0.019 A @ 24 VDC (without internal field circuit supply)
    0.115 A @ 24 VDC (32-channel dry contact with internal field circuit supply)
  • 65M-2901-CT-T:
    0.005 A @ 24 VDC
  • 65M-3600-CT-T:
    0.053 A @ 24 VDC (without internal loop power)
    0.466 A @ 24 VDC (16-channel 20 mA current input with internal loop power)
  • 65M-3610-CT-T:
    0.038 A @ 24 VDC
  • 65M-4820-CT-T:
    0.022 A @ 24 VDC (without external load)
    0.266 A @ 24 VDC (4 channels with 20 mA current output)

Field Power

  • 65M-1900-CT-T/65M-2901-CT-T:
    0.068 A @ 12 VDC
  • 65M-3610-CT-T/65M-4820-CT-T:
    0.069 A @ 12 VDC
  • 65M-3600-CT-T:
    0.073 A @ 12 VDC

Housing

  • Plastic

Dimensions

  • 42 x 116 x 130 mm (1.65 x 4,57 x 5.12 in)

Weight

  • 65M-1900-CT-T: 253 g (0.56 lb)
  • 65M-2901-CT-T: 254 g (0.56 lb)
  • 65M-3600-CT-T: 267 g (0.59 lb)
  • 65M-3610-CT-T: 250 g (0.55 lb)
  • 65M-4820-CT-T: 257 g (0.57 lb)

Operating Temperature

  • -40 to 75°C (-40 to 167°F)
    Note: Proper airflow is required in an environment with temperature > 65°C.

Storage Temperature (package included)

  • -40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

  • 5 to 95% (non-condensing)

Altitude

  • Up to 2000 meters 

EMC

  • EN 55032/35
  • EN 61000-6-2/-6-4

EMI

  • CISPR 32, FCC Part 15B Class A

EMS

  • IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
  • IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
  • IEC 61000-4-4 EFT: Power: (DC) 1 kV; Signal: 1 kV
  • IEC 61000-4-5 Surge: Power: (DC) 0.5 kV L-N, 1 kV L/N-PE; Signal: 1 kV; IO: 0.5 kV
  • IEC 61000-4-6 CS: Power: (DC) 10
  • Vrms; Signal: 10 Vrms
  • IEC 61000-4-8 PFMF: 30 A/m

Safety

  • UL 61010-1
  • UL 61010-2-201

Shock

  • IEC 60068-2-27
  • Half sine wave; acceleration: 15 g; time: 11 ms

Vibration

  • IEC 60068-2-6
  • DIN-rail mounted:
    7 mm peak-peak (p-p) (2 to 8.42 Hz), 1 g (8.42 to 150 Hz)
  • Rack mounted (with optional kit):
    7 mm peak-peak (p-p) (2 to 8.42 Hz), 0.5 g (8.42 to 150 Hz)

Time

  • 65M-1900-CT-T: 2,057,118 hrs
  • 65M-2901-CT-T: 2,007,795 hrs
  • 65M-3600-CT-T: 1,686,798 hrs
  • 65M-3610-CT-T: 1,885,953 hrs
  • 65M-4820-CT-T: 1,874,152 hrs

Standards

  • Telcordia Standard SR-332

Warranty Period

  • 5 years