MGate 5192 Series

Features and Benefits

Overview

The MGate 5192 is an industrial protocol gateway for converting IEC 61850 MMS to Modbus RTU/ASCII/TCP, DNP3 serial/TCP/UDP, IEC 60870-5- 101, or IEC 60870-5-104 communications. To integrate existing IEC 61850 devices, such as IEDs or relays, into a Modbus, DNP3, IEC 101, or IEC 104 network, use the MGate 5192 as an IEC 61850 MMS client to collect and exchange data with Modbus RTU/ASCII/TCP, DNP3 serial/TCP/UDP, IEC 60870-5-101, or IEC 60870-5-104 SCADA/devices. All models are protected by a rugged and compact metal housing, are DIN-rail mountable, and offer built-in serial isolation. The rugged design is suitable for industrial applications such as power substation and renewable energy-related applications.

Easy Configuration

  • The MGate 5192 gateways are provided with a web console to make configuration easy without having to install an extra utility. In addition, HTTPS encryption of communication ensures higher network security. In most data-acquisition applications, configuration of devices with Modbus commands can be time-consuming and increase costs. The MGate 5192 gateways provide offline configuration via a CSV file to help complete the Modbus settings quickly. The MGate gateways provide software-configurable pull high/low and termination resistor settings for RS-485 2-wire to reduce efforts by eliminating the need to open the chassis.

Easy Troubleshooting

  • The MGate 5192 gateways provide a variety of maintenance functions to reduce troubleshooting time and cost, including LED indicators, protocol diagnostics, traffic monitor, and tag view. These tools help you capture and check data to easily identify the root cause of issues, especially during the installation stage. The MGate gateways also come with status monitoring and fault protection functions. The status monitoring function notifies a SCADA system when a IEC 61850 device gets disconnected or does not respond, in which case the process SCADA gets the status of each end device and then issues alarms to notify operators. The fault protection function keeps the latest data without sending output data to the IEC 61850 devices. When a SCADA gets disconnected, the end devices keep the last operation and do not go offline.

Specifications

Ethernet Interface

10/100BaseT(X) Ports (RJ45 connector)

  • 2
  • Auto MDI/MDI-X connection

Magnetic Isolation Protection

  • 1.5 kV (built-in)

Industrial Protocols:

  • IEC 61850 MMS Client
  • Modbus TCP Server
  • IEC 60870-5-104 Server
  • DNP3 TCP/UDP Outstation

Configuration Options:

  • Web Console (HTTPS)
  • Device Search Utility (DSU)

Management:

  • ARP
  • DHCP Client
  • DNS
  • HTTP
  • HTTPS
  • SMTP
  • SNMP Trap
  • SNMPv1/v2c/v3
  • TCP/IP
  • UDP

MIB:

  • RFC1213
  • RFC1317

Time Management:

  • NTP Client 

Authentication:

  • Local database

Encryption:

  • HTTPS
  • AES-128
  • AES-256
  • SHA-256

Security Protocols:

  • SNMPv3
  • SNMPv2c Trap
  • HTTPS (TLS 1.3)

No. of Ports

  • 1

Connector

  • DB9 male

Serial Standards

  • RS-232/422/485

Baudrate

  • 300 bps to 921.6 kbps

Data Bits

  • 7, 8

Parity

  • None
  • Even
  • Odd
  • Space
  • Mark

Stop Bits

  • 1, 2

Flow Control

  • RTS Toggle (RS-232 only)
  • RTS/CTS

RS-485 Data Direction Control

  • Automatic Data Direction Control (ADDC)

Pull High/Low Resistor for RS-485

  • 1 kilo-ohm
  • 150 kilo-ohms
  • software configurable

Terminator for RS-485

  • 120 ohms
  • software configurable

Isolation

  • 2 kV (built-in)

RS-232

  • TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND

RS-422

  • Tx+, Tx-, Rx+, Rx-, GND

RS-485-2w

  • Data+, Data-, GND

RS-485-4w

  • Tx+, Tx-, Rx+, Rx-, GND

Industrial Protocols

  • Modbus RTU/ASCII Server
  • IEC 60870-5-101 Server
  • DNP3 Serial Outstation

Mode

  • MMS Client

Max. No. of Server Connections

  • 32

Max. No. of Data Objects

  • 5000 points

Mode:

  • Server

Functions Supported

  • 1, 2, 3, 4, 5, 6, 15, 16, 23

Max. No. of Client Connections

  • 16

Max. No. of Data Tags

  • 5000 tags

Mode

  • Server

Functions Supported

  • 1, 2, 3, 4, 5, 6, 15, 16, 23

Max. No. of Client Connections

  • 1

Max. No. of Data Tags

  • 5000 tags

Mode

  • Outstation

Objects Supported

  • Binary inputs
  • Analog inputs
  • Counters
  • Frozen counters
  • Binary outputs
  • Analog outputs

Max. No. of Client Connections

  • 1

Protocol Security

  • Secure Authentication v5

Max. No. of Objects

  • 5000 points

Mode

  • Outstation

Objects Supported

  • Binary inputs
  • Analog inputs
  • Counters
  • Frozen counters
  • Binary outputs
  • Analog outputs

Max. No. of Client Connections

  • 1

Max. No. of Objects

  • 5000 points

Mode

  • Server (balanced/unbalanced)

Objects Supported

  • Single point
  • Double point
  • Step position
  • Bit string of 32 bit
  • Measured value (normalized)
  • Measured value (scaled)
  • Measured value (floating)
  • Integrated totals

Max. No. of Client Connections

  • 1

Max. No. of Information Objects

  • 5000 points

Mode

  • Server 

Objects Supported

  • Single point
  • Double point
  • Step position
  • Bit string of 32 bit
  • Measured value (normalized)
  • Measured value (scaled)
  • Measured value (floating)
  • Integrated totals

Max. No. of Client Connections

  • 32

Max. No. of Information Objects

  • 5000 points

microSD Slot

  • Up to 32 GB (SD 2.0 compatible)

Input Voltage

  • 12 to 48 VDC

Input Current

  • 455 mA (max)

Power Connector

  • Spring-type Euroblock terminal

Contact Current Rating

  • Resistive load: 2 A @ 30 VDC

Housing

  • Metal

IP Rating

  • IP30

Dimensions

  • 25 x 90 x 129.6 mm (0.98 x 3.54 x 5.1 in)

Weight

  • 294 g (0.65 lb)

Operating Temperature:

  • -40 to 75°C (-40 to 167°F)

Storage Temperature (package included):

  • -40 to 85°C (-40 to 185°F)

Ambient Relative Humidity:

  • 5 to 95% (non-condensing)

Safety

  • EN 61010-2-201
  • UL 61010-2-201

EMC

  • EN 61000-6-2/-6-4

EMI

  • FCC Part 15B Class A

EMS

  • IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
  • IEC 61000-4-3 RS: 80 MHz to 1 GHz: 20 V/m
  • IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV
  • IEC 61000-4-5 Surge: Power: 2 kV; Signal: 4 kV
  • IEC 61000-4-6 CS: 10 V/m
  • IEC 61000-4-8 PFMF: 100 A/m

Shock

  • IEC 60068-2-27

Vibration

  • IEC 60068-2-6
  • IEC 60068-2-64

Power Substation

  • IEEE 1613
  • IEC 61850-3

International Approval

  • UKCA
  • KC

Time

  • 1,240,821 hrs

Standards

  • Telcordia SR332

Warranty Period: 

  • 5 years