ioLogik E2200 Series

Features and Benefits

Overview

Moxa’s ioLogik E2200 Series Ethernet Remote I/O is a PC-based data acquisition and control device that uses proactive, event-based reporting to control I/O devices and features the Click&Go programming interface. Unlike traditional PLCs, which are passive and must poll for data, Moxa’s ioLogik E2200 Series will, when paired with our MX-AOPC UA Server, communicate with SCADA systems using active messaging that is pushed to the server only when state changes or configured events occur. Additionally, the ioLogik E2200 features SNMP for communications and control using an NMS (Network Management System), allowing IT professionals to configure the device to push I/O status reports according to configured specifications. This report-by-exception approach, which is new to PC-based monitoring, requires far less bandwidth than traditional polling methods.

PC-Free Alarm and Control Intelligence

  • This device supports simple yet powerful Click&Go™ technology to configure event-driven reports and alarms delivered over email, TCP/UDP, or SNMP traps, giving you a powerful and effective tool for delivering timestamped status updates in real time.
  • With built-in Click&Go™ intelligence, this device can be configured for simple outputs paired up with simple input triggers without the need for a PC controller. This allows it to be configured to automatically report I/O events according to conditions specified by the user.

SNMP for Ethernet Device Management

  • By using SNMP, IT engineers can configure the device to deliver alarms (traps) for specific I/O events, or use it to read or write directly to the I/O registers. For the strongest security, the device features SNMPv3, with authentication and encryption. With Moxa’s SNMP-capable I/O, even IT professionals can easily integrate industrial sensors and servos over an Ethernet backbone, and with its strong network management tools, it is ideal for a wide variety of industrial applications, including environmental monitoring, telecommunications, power production and delivery, and transportation.

Push Technology for Events and Alarms

  • When used with MX-AOPC UA Server, devices can use active push communications when communicating changes in state and/or events to a SCADA system. Unlike a polling system, when using a push architecture for communications with a SCADA system, messages will only be delivered when changes in state or configured events occur, resulting in higher accuracy and lower amounts of data that need to be transferred.

Specifications

Control Logic

Language: 

  • Click&Go

Digital Input Channels

  • ioLogik E2210 Series: 12
  • ioLogik E2212 Series: 8
  • ioLogik E2214 Series: 6

Digital Output Channels

  • ioLogik E2210/E2212 Series: 8
  • ioLogik E2260/E2262 Series: 4

Configurable DIO Channels (by software)

  • ioLogik E2212 Series: 4
  • ioLogik E2242 Series: 12

Relay Channels

  • ioLogik E2214 Series: 6

Analog Input Channels

  • ioLogik E2240 Series: 8
  • ioLogik E2242 Series: 4

Analog Output Channels

  • ioLogik E2240 Series: 2

RTD Channels

  • ioLogik E2260 Series: 6

Thermocouple Channels

  • ioLogik E2262 Series: 8

Buttons

  • Reset button

Rotary Switch

  • 0 to 9

Isolation

  • 3k VDC or 2k Vrms

Connector:

  • Screw-fastened Euroblock terminal

Sensor Type:

  • ioLogik E2210 Series: Dry Contact and Wet Contact (NPN)
  • ioLogik E2212/E2214/E2242 Series: Dry Contact and Wet Contact (NPN or PNP)

I/O Mode:

  • DI or event counter

Dry Contact:

  • On: short to GND
  • Off: open

Wet Contact (DI to COM):

  • On: 0 to 3 VDC
  • Off: 10 to 30 VDC

Counter Frequency:

  • 900 Hz

Digital Filtering Time Interval:

  • Software configurable

Points per COM:

  • ioLogik E2210 Series: 12 channels
  • ioLogik E2212/E2242 Series: 6 channels
  • ioLogik E2214 Series: 3 channels

Connector:

  • Screw-fastened Euroblock terminal

I/O Type:

  • Sink

I/O Mode:

  • DO or pulse output

Current Rating:

  • 200 mA per channel

Pulse Output Frequency:

  • 1 kHz

DIO Output Leakage Current:

  • 4.0 mA @ 24 VDC

Over-Current Protection:

  • 0.65 A per channel @ 25°C

Over-Temperature Shutdown:

  • 175°C (min.)

Over-Voltage Protection:

  • 45 VDC (typical)

Connector

  • Screw-fastened Euroblock terminal

Type

  • Form A (N.O.) power relay

I/O Mode

  • Relay or pulse output

Pulse Output Frequency

  • 0.3 Hz at rated load

Contact Current Rating

  • Inductive load: 2 A @ 30 VDC, 250 VAC, 110 VAC
  • Resistive load: 5 A @ 30 VDC, 250 VAC, 110 VAC

Minimum Permitted Load

  • 1 A @ 5 VDC

Contact Resistance

  • 100 milli-ohms (max.)

Electrical Endurance

  • 100,000 operations @ 5 A resistive load

Mechanical Endurance

  • 1,000,000 operations

Note

  • Ambient humidity must be non-condensing and remain between 5 and 95%.
  • The relays may malfunction when operating in high condensation environments below 0°C.

Connector

  • Screw-fastened Euroblock terminal

I/O Mode

  • Voltage/Current

I/O Type

  • Differential

Resolution

  • 16 bits

Input Range

  • ioLogik E2240 Series: ±150 mV, ±500 mV, ±5 V, ±10 V, 0 to 20 mA, 4 to 20 mA
  • ioLogik E2242 Series: ±150 mV, 0 to 150 mV, ±500 mV, 0 to 500 mV, ±5 V, 0 to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA

Accuracy

  • ioLogik E2240/E2242:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C

  • ioLogik E2240-T/E2242-T:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C
    ±0.5% FSR @ -40 to 75°C

Sampling Rate

  • ioLogik E2240 Series:
    All Channels: 10 samples/sec for voltage; 6 samples/sec for current
    Per Channel: 1.25 samples/sec for voltage; 0.75 samples/sec for current
    Single channel: 1.25 samples/sec for voltage; 0.75 samples/sec for current

  • ioLogik E2242 Series:
    All channels: 32 samples/sec
    Per channel: 8 samples/sec
    Single channel: 100 samples/sec

Built-in Resistor for Current Input

  • 120 ohms

Input Impedance

  • ioLogik E2240 Series: 900 kilo-ohms (min.)
  • ioLogik E2242 Series: 200 kilo-ohms (min.)

Over-Voltage Protection

  • -25 to +30 VDC (power on)
  • -35 to +35 VDC (power off)

Connector

  • Screw-fastened Euroblock terminal

I/O Mode

  • Voltage/Current

Output Range

  • 0 to 10 VDC
  • 4 to 20 mA

Resolution

  • 12-bit

Accuracy

  • ioLogik E2240:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C

  • ioLogik E2240-T:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C
    ±0.5% FSR @ -40 to 75°C

Load (Current Mode)

  • Internal power: 250 ohms (max.)

Connector

  • Screw-fastened Euroblock terminal

Sensor Type

  • JPT100, JPT200, JPT500 (-200 to 640°C)
  • JPT1000 (-200 to 350°C)
  • NI100, NI200, NI500 (-60 to 250°C)
  • NI1000 (-60 to 150°C)
  • NI120 (-80 to 260°C)
  • PT1000 (-200 to 350°C)
  • PT50, PT100, PT200, PT500 (-200 to 850°C)
  • Resistance of 310, 620, 1250, and 2200 ohms

Input Connection

  • 2- or 3-wire

Sampling Rate

  • All channels: 12 samples/sec
  • Per channel: 2 samples/sec

Resolution

  • 0.1°C or 0.1 ohms

Accuracy

  • ioLogik E2260:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C

  • ioLogik E2260-T:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C
    ±0.5% FSR @ -40 to 75°C

Input Impedance

  • 625 kilo-ohms (min.)

Connector

  • Screw-fastened Euroblock terminal

Sensor Type

  • J, K, T, E, R, S, B, N

Millivolt Type

  • ±19.532 mV
  • ±39.062 mV
  • ±78.126 mV
  • Fault and over-voltage protection: -35 to +35 VDC (power off)
  • -25 to +30 VDC (power on)

Resolution

  • 16 bits

Millivolt Accuracy

  • ioLogik E2262:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C

  • ioLogik E2262-T:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C
    ±0.5% FSR @ -40 to 75°C

TC Accuracy

  • Types J, T, E, S, B: ±5°C
  • Types K, R, N: ±8°C

CJC Accuracy

  • ±0.5°C @ 25°C
  • ±1.5°C @ -40 to 75°C

Sampling Rate

  • All channels: 12 samples/sec
  • Per channel: 1.5 samples/sec

Input Impedance

  • 1 mega-ohms (min.)

LED Indicators

  • PWR
  • RDY
  • Serial
  • I/O Status

10/100BaseT(X) Ports (RJ45 connector)

  • 1

Magnetic Isolation Protection

  • 1.5 kV (built-in)

Configuration Options

  • Windows Utility (ioAdmin)
  • Web Console (HTTP)

Industrial Protocols

  • Modbus TCP Server (Slave)
  • SNMPv1/v2c/v3
  • SNMPv1 Trap
  • Moxa AOPC (Active Tag)
  • MXIO Library
  • CGI commands

Management

  • BOOTP
  • IPv4
  • SMTP
  • DHCP Client
  • HTTP
  • TCP/IP

MIB

  • Device Settings MIB

Time Management

  • SNTP

Authentication

  • Local database

Encryption

  • HMAC

Security Protocols

  • SNMPv3

Functions Supported

  • 1, 2, 3, 4, 5, 6, 15, 16

Mode

  • Server (Slave)

Connector

  • Terminal block

Serial Standards

  • RS-485

No. of Ports

  • 1

Baudrate

  • 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps

Parity

  • None

Data Bits

  • 8

Stop Bits

  • 1

Flow Control

  • None

RS-485-2w

  • Data+, Data-, GND

Industrial Protocols

  • Modbus RTU Master

Real-time Clock (RTC)

  • Real-time clock with battery backup

Power Connector

  • Screw-fastened Euroblock terminal

No. of Power Inputs

  • 1

Input Voltage

  • 12 to 36 VDC

Power Consumption

  • ioLogik E2210 Series: 202 mA @ 24 VDC
  • ioLogik E2212 Series: 136 mA @ 24 VDC
  • ioLogik E2214 Series: 170 mA @ 24 VDC
  • ioLogik E2240 Series: 198 mA @ 24 VDC
  • ioLogik E2242 Series: 178 mA @ 24 VDC
  • ioLogik E2260 Series: 95 mA @ 24 VDC
  • ioLogik E2262 Series: 160 mA @ 24 VDC

Housing

  • Plastic

Dimensions

  • 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)

Weight

  • 250 g (0.55 lb)

Installation

  • DIN-rail mounting
  • Wall mounting

Wiring

  • I/O cable, 16 to 26 AWG
  • Power cable, 16 to 26 AWG

Operating Temperature

  • Standard Models: -10 to 60°C (14 to 140°F)
  • Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature (package included)

  •  -40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

  • 5 to 95% (non-condensing)

Altitude

  • 2000 m 

Safety

  • UL 508

EMC

  • EN 61000-6-2/-6-4

EMI

  • CISPR 32, FCC Part 15B Class A

EMS

  • IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
  • IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
  • IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
  • IEC 61000-4-5 Surge: Power: 1 kV
  • IEC 61000-4-6 CS: 10 V
  • IEC 61000-4-8 PFMF

Shock

  • IEC 60068-2-27

Freefall

  • IEC 60068-2-32

Vibration

  • IEC 60068-2-6

Green Product

  • RoHS
  • CRoHS
  • WEEE

Time

  • ioLogik E2210 Series: 213,673 hrs
  • ioLogik E2212 Series: 217,722 hrs
  • ioLogik E2214 Series: 307,329 hrs
  • ioLogik E2240 Series: 155,941 hrs
  • ioLogik E2242 Series: 204,391 hrs
  • ioLogik E2260 Series: 327,282 hrs
  • ioLogik E2262 Series: 341,063 hrs

Standards

  • Telcordia SR332

Warranty Period: 

  • ioLogik E2214 Series: 2 years 
  • ioLogik E2210/E2212/E2240/E2242/E2260/E2262 Series: 5 years