ioLogik E1200 Series

Features and Benefits

Overview

The ioLogik E1200 Series supports the most often-used protocols for retrieving I/O data, making it capable of handling a wide variety of applications. Most IT engineers use SNMP or RESTful API protocols, but OT engineers are more familiar with OT-based protocols, such as Modbus and EtherNet/IP. Moxa’s Smart I/O makes it possible for both IT and OT engineers to conveniently retrieve data from the same I/O device. The ioLogik E1200 Series speaks six different protocols, including Modbus TCP, EtherNet/IP, and Moxa AOPC for OT engineers, as well as SNMP, RESTful API, and Moxa MXIO library for IT engineers. The ioLogik E1200 retrieves I/O data and converts the data to any of these protocols at the same time, allowing you to get your applications connected easily and effortlessly.

Daisy-Chained Ethernet I/O Connection

  • This industrial Ethernet remote I/O comes with two switched Ethernet ports to allow for the free flow of information downstream to another local Ethernet device, or upstream to a control server via expandable daisy-chained Ethernet I/O arrays. Applications such as factory automation, security and surveillance systems, and tunneled connections can make use of daisy-chained Ethernet for building multidrop I/O networks over standard Ethernet cables. Many industrial automation users are familiar with multidrop as the configuration most typically used in fieldbus solutions. The daisy-chain capabilities supported by ioLogik Ethernet remote I/O units not only increase the expandability and installation possibilities for your remote I/O applications, but also lower overall costs by reducing the need for separate Ethernet switches. Daisy-chaining devices in this way will also reduce overall labor and cabling expenses.

Save Time and Wiring Costs with Peer-to-Peer Communications

  • In remote automation applications, the control room and sensors are often far removed, making wiring over long distances a constant challenge. With peer-to-peer networking, users may now map a pair of ioLogik Series modules so that input values will be directly transferred to output channels, greatly simplifying the wiring process and reducing wiring costs.

User-Definable Modbus TCP Addressing for Painless Upgrading of Existing Systems

  • For Modbus devices that are controlled and detected by fixed addresses, users need to spend a vast amount of time researching and verifying initial configurations. Users need to locate each device’s networking details, such as I/O channels or vendor-defined addresses, to enable the initial or start address of a SCADA system or PLC. Devices that support user-definable Modbus TCP addressing offer greater flexibility and easier setup. Instead of worrying about individual devices, users simply configure the function and address map to fit their needs.

Push Technology for Events

  • When used with MX-AOPC UA Server, devices can use active push communications when communicating changes in state and/or events to a SCADA system. Unlike a polling system, when using a push architecture for communications with a SCADA system, messages will only be delivered when changes in state or configured events occur, resulting in higher accuracy and lower amounts of data that need to be transferred.

Specifications

Input/Output Interface

Digital Input Channels

  • ioLogik E1210 models: 16
  • ioLogik E1212/E1213 models: 8
  • ioLogik E1214 models: 6
  • ioLogik E1242 models: 4

Digital Output Channels

  • ioLogik E1211 models: 16
  • ioLogik E1213 models: 4

Configurable DIO Channels (by jumper)

  • ioLogik E1212 models: 8
  • ioLogik E1213/E1242 models: 4

Relay Channels

  • ioLogik E1214 models: 6

Analog Input Channels

  • ioLogik E1240 models: 8
  • ioLogik E1242 models: 4

Analog Output Channels

  • ioLogik E1241 models: 4

RTD Channels

  • ioLogik E1260 models: 6

Thermocouple Channels

  • ioLogik E1262 models: 8

Isolation

  • 3k VDC or 2k Vrms

Buttons

  • Reset button

Connector:

  • Screw-fastened Euroblock terminal

Sensor Type:

  • Dry contact
  • Wet contact (NPN or PNP)

I/O Mode:

  • DI or event counter

Dry Contact:

  • On: short to GND
  • Off: open

Wet Contact (DI to COM):

ioLogik E1210/E1212/E1213/E1214/E1242 models:

  • On: 10 to 30 VDC
  • Off: 0 to 3 VDC

Counter Frequency:

  • 250 Hz

Digital Filtering Time Interval:

  • Software configurable

Points per COM:

  • ioLogik E1210/E1212 models: 8 channels
  • ioLogik E1213 models: 12 channels
  • ioLogik E1214 models: 6 channels
  • ioLogik E1242 models: 4 channels

Connector:

  • Screw-fastened Euroblock terminal

I/O Type:

  • ioLogik E1211/E1212/E1242 models: Sink
  • ioLogik E1213 models: Source

I/O Mode:

  • DO or pulse output

Current Rating:

  • ioLogik E1211/E1212/E1242 models: 200 mA per channel
  • ioLogik E1213 models: 500 mA per channel

Pulse Output Frequency:

  • 500 Hz (max.)

Over-Current Protection:

  • ioLogik E1211/E1212/E1242 models: 2.6 A per channel @ 25°C
  • ioLogik E1213 models: 1.5 A per channel @ 25°C

Over-Temperature Shutdown:

  • 175°C (typical)
  • 150°C (min.)

Over-Voltage Protection:

  • 35 VDC

Connector

  • Screw-fastened Euroblock terminal

Type

  • Form A (N.O.) power relay

I/O Mode

  • Relay or pulse output

Pulse Output Frequency

  • 0.3 Hz at rated load (max.)

Contact Current Rating

  • ioLogik E1214/E1214-T models:
    Resistive load:
    5A @ 30 VDC, 250 VAC, 110 VAC

Contact Resistance

  • 100 milli-ohms (max.)

Mechanical Endurance

  • 5,000,000 operations

Electrical Endurance

  • 100,000 operations @ 5 A resistive load

Breakdown Voltage

  • 500 VAC

Initial Insulation Resistance

  • 1,000 mega-ohms (min.) @ 500 VDC

Note

  • Ambient humidity must be non-condensing and remain between 5 and 95%.
  • The relays may malfunction when operating in high condensation environments below 0°C.

Connector

  • Screw-fastened Euroblock terminal

I/O Mode

  • Voltage/Current

I/O Type

  • Differential

Resolution

  • 16 bits

Input Range

  • 0 to 10 VDC
  • 0 to 20 mA
  • 4 to 20 mA
  • 4 to 20 mA (with burn-out detection)

Accuracy

  • ioLogik E1240/E1242:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C

  • ioLogik E1240-T/E1242-T:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C
    ±0.5% FSR @ -40 to 75°C

Sampling Rate

  • ioLogik E1240: 12 samples/sec per module (shared between up to 8 channels) 
  • ioLogik E1242: 12 samples/sec per module (shared between up to 4 channels) 

Built-in Resistor for Current Input

  • 120 ohms

Input Impedance

  • 10 mega-ohms (min.)

Connector

  • Screw-fastened Euroblock terminal

I/O Mode

  • Voltage/Current

Output Range

  • 0 to 10 VDC
  • 0 to 20 mA
  • 4 to 20 mA

Resolution

  • 12-bit

Accuracy

  • ioLogik E1241:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C
  • ioLogik E1241-T:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -40 to 75°C

Load (Current Mode)

  • Internal power: 400 ohms (max.)
  • 24 V external power: 1000 ohms (max.)

Voltage Output Short-Circuit Protection

  • 10 mA

Connector

  • Screw-fastened Euroblock terminal

Sensor Type

  • PT1000 (-200 to 350°C)
  • PT50
  • PT100
  • PT200
  • PT500 (-200 to 850°C)

Resistance Type

  • 310, 620, 1250, and 2200 ohms

Input Connection

  • 2- or 3-wire

Sampling Rate

  • ioLogik E1260: 12 samples/sec per module (shared between up to 6 channels) 

Resolution

  • 0.1°C or 0.1 ohms

Accuracy

  • ioLogik E1260:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C

  • ioLogik E1260-T:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -40 to 75°C

Input Impedance

  • 625 kilo-ohms (min.)

Connector

  • Screw-fastened Euroblock terminal

Sensor Type

  • J, K, T, E, R, S, B, N

Millivolt Type

  • ±19.532 mV
  • ±39.062 mV
  • ±78.126 mV
  • Fault and over-voltage protection: -35 to +35 VDC (power off)
  • -25 to +30 VDC (power on)

Resolution

  • 16 bits

Millivolt Accuracy

  • ioLogik E1262:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 to 60°C

  • ioLogik E1262-T:
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -40 to 75°C

TC Accuracy

  • Types J, T, E, S, B: ±5°C
  • Types K, R, N: ±8°C

CJC Accuracy

  • ±0.5°C @ 25°C
  • ±1.5°C @ -40 to 75°C

Sampling Rate

  • ioLogik E1262: 12 samples/sec per module (shared between up to 8 channels) 

Input Impedance

  • 10 mega-ohms (min.)

10/100BaseT(X) Ports (RJ45 connector)

  • 2, 1 MAC address (Ethernet bypass)

Magnetic Isolation Protection

  • 1.5 kV (built-in)

Configuration Options

  • Web Console (HTTP)
  • Windows Utility (ioSearch)
  • MCC Tool

Industrial Protocols

  • Modbus TCP Server (Slave)
  • Moxa AOPC (Active Tag)
  • MXIO Library
  • EtherNet/IP Adapter

Management

  • RESTful API
  • SNMPv1/v2c
  • SNMPv1 Trap
  • HTTP
  • DHCP Client
  • BOOTP
  • IPv4
  • TCP/IP
  • UDP

MIB

  • Device Settings MIB

Security

  • Access control list

Authentication

  • Local database

LED Indicators

  • Power
  • Ready
  • Port 1
  • Port 2

Functions Supported

  • 1, 2, 3, 4, 5, 6, 15, 16, 23

Mode

  • Server (Slave)

Max. No. of Client Connections

  • 10

Mode

  • Adapter

Max. No. of Scanner Connections

  • 9 (for read-only)
  • 1 (for read/write)

Power Connector

  • Screw-fastened Euroblock terminal

No. of Power Inputs

  • 1

Input Voltage

  • 12 to 36 VDC

Power Consumption

  • ioLogik E1210 models: 110 mA @ 24 VDC
  • ioLogik E1211 models: 200 mA @ 24 VDC
  • ioLogik E1212 models: 155 mA @ 24 VDC
  • ioLogik E1213 models: 130 mA @ 24 VDC
  • ioLogik E1214 models: 188 mA @ 24 VDC
  • ioLogik E1240 models: 121 mA @ 24 VDC
  • ioLogik E1241 models: 194 mA @ 24 VDC
  • ioLogik E1242 models: 139 mA @ 24 VDC
  • ioLogik E1260 models: 110 mA @ 24 VDC
  • ioLogik E1262 models: 118 mA @ 24 VDC

Housing

  • Plastic

Dimensions

  • 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)

Weight

  • 200 g (0.44 lb)

Installation

  • DIN-rail mounting
  • Wall mounting

Wiring

  • I/O cable, 16 to 26 AWG
  • Power cable, 12 to 24 AWG

Operating Temperature

  • Standard models: -10 to 60°C (14 to 140°F)
  • Wide temp. models: -40 to 75°C (-40 to 167°F)

Storage Temperature (package included)

  •  -40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

  • 5 to 95% (non-condensing)

Altitude

  • 4000 m 

EMC

  • EN 55032/24
  • EN 61000-6-2/-6-4

EMI

  • CISPR 32, FCC Part 15B Class A

EMS

  • IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
  • IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
  • IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
  • IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
  • IEC 61000-4-6 CS: 10 V
  • IEC 61000-4-8 PFMF

Hazardous Locations

  • ATEX
  • Class I Division 2

Safety

  • UL 508

Shock

  • IEC 60068-2-27

Freefall

  • IEC 60068-2-32

Vibration

  • IEC 60068-2-6

Green Product

  • RoHS
  • CRoHS
  • WEEE

Time

  • ioLogik E1210 models: 671,345 hrs
  • ioLogik E1211 models: 923,027 hrs
  • ioLogik E1212 models: 561,930 hrs
  • ioLogik E1213 models: 715,256 hrs
  • ioLogik E1214 models: 808,744 hrs
  • ioLogik E1240 models: 474,053 hrs
  • ioLogik E1241 models: 888,656 hrs
  • ioLogik E1242 models: 502,210 hrs
  • ioLogik E1260 models: 660,260 hrs
  • ioLogik E1262 models: 631,418 hrs

Standards

  • Telcordia Standard SR-332

Warranty Period: 

  • ioLogik E1214: 2 years 
  • ioLogik E1210/E1211/E1212/E1213/E1240/E1241/E1242/E1260/E1262: 5 years