HPH Series 160/200 kVA

Features and Benefits

Overview

The Ultron HPH series 160-200 kVA is a true online double-conversion UPS offering the best-in-class combination of power performance and efficiency for medium data centers, pan-IT, and other mission critical applications. Thanks to Delta‘s R&D expertise and excellent engineering capabilities, the Ultron HPH features up to 96.5% AC-AC efficiency, low iTHD < 3%, and high input power factor > 0.99 resulting in significant total cost of ownership (TCO) savings. Highlights of the highly reliable Ultron HPH series UPS design include key component redundancy and proactive battery health detection. With its combination of superior availability and power performance, the Ultron HPH 160-200 kVA is the top choice for power protection of sustainable medium business operations.

Specifications

Model

HPH-160K / HPH-200K

HPH-160K

  • 160 kVA* / 150 kW

HPH-200K

  • 200 kVA / 200 kW

Nominal Voltage

  • 220/380 Vac
  • 230/400 Vac
  • 240/415 Vac (3-phase, 4-wire + G)

Voltage Range

  • 305~478 Vac (full load)
  • 228~478 Vac (70% load)

Current Harmonic Distortion

  • ≤ 3% **

Frequency 

  • 40~70 Hz

Voltage

  • 220/380 Vac
  • 230/400 Vac
  • 240/415 Vac (3-phase, 4-wire + G)

Voltage Harmonic Distortion

  • ≤ 0.5% (linear load)

Frequency 

  • 50/60 Hz

Frequency Regulation

  • ± 0.05 Hz (battery mode)

Overload Capability

  • ≤ 125%: 10 minutes
  • ≤ 150%: 1 minute

Display

  • 10” color touch screen
  • Standard
    External battery temperature detection x 4, External switch/breaker status dry contact x 4, Output dry contact x 6, Input dry contact x 4, Parallel port x 2, USB Port (Type A x 2; Type B x 1), RS232 Port x 1, Modbus Port x 1, BMS (RJ45) x 1, Ethernet x 1, SNMP Slot x 1, REPO Port x 1
  • Optional
    Relay I/O card, Battery cabinet temperature sensor cable

Safety

  • CE
  • RCM

UPS Classification According to IEC 62040-3

  • VFI-SS-111

AC-AC

  • Up to 96.5%

ECO Mode

  • 99%

Nominal Voltage

  • ±240 Vdc

Charge Voltage

  • ± 272 Vdc (adjustable from 204 V to 312 V)

Battery Number Configuration

  • 30~46 pcs (default: 40 pcs)

Operating Altitude

  • 1000 meters (without derating)

Operating Temperature

  • 0~40℃

Relative Humidity

  • 0~95% (non-condensing)

Parallel Redundancy and Expansion

  • Maximum 8 units

Remote Emergency Power Off

  • Yes

Battery Start

  • Yes

Dimensions (W x D x H) 

  • 600 x 1100 x 1600 mm

Weight

  • HPH-160K : 339 kg
  • HPH-200K : 376 kg