HPH Gen2 Series 20/30/40 kVA

Features and Benefits

Overview

The latest HPH Gen2 20-40 kVA UPS offers a best in class footprint and high-level performance. With advanced technology and thermal management, it achieves the world’s leading power density and promises 40°C without de-rating. The 0.99 input PF and iTHD < 2% ensure maximum upstream source compatibility. Low total cost of ownership is achieved by > 96% efficiency, energy recycle mode, wider battery quantity configuration and inbuilt 15 A charger. In addition, it provides a user-friendly interface touch panel, manual protection devices and caster wheels for easy deployment, installation and operation. All these features provide the ideal solution for various small and medium-sized data centers and critical power backups.

Specifications

Model
  • Long Backup Model:
    HPH-20K / HPH-30K / HPH-40K
  • Inbuilt Battery Model – Batteries Inside:
    HPH-20KB / HPH-30KB / HPH-40KB
  • Inbuilt battery model – No Batteries Inside:
    HPH-20KB-N / HPH-30KB-N / HPH-40KB-N

HPH-20K/B/B-N

  • 20 kVA / 20 kW

HPH-30K/B/B-N

  • 30 kVA / 30 kW

HPH-40K/B/B-N

  • 40 kVA / 40 kW

Nominal Voltage

  • 220/380 Vac
  • 230/400 Vac
  • 240/415 Vac (3-phase, 4-wire + G)

Voltage Range

  • 305-478 Vac (full load)
  • 228-305 Vac (with derating to 70-100%)

Current Harmonic Distortion

  • HPH-20K/B/B-N: ≤ 2.5%
  • HPH-30K/B/B-N: ≤ 2%
  • HPH-40K/B/B-N: ≤ 2%

Power Factor

  • > 0.99

Frequency Range

  • 40~70 Hz

Voltage

  • 220/380 Vac
  • 230/400 Vac
  • 240/415 Vac (3-phase, 4-wire + G)

Voltage Harmonic Distortion

  • ≤ 1.5% (linear load)
  • ≤ 4% (non-linear load)

Voltage Regulation

  • ± 1% (static)

Frequency 

  • 50/60 Hz

Overload Capability

  • ≤ 105%: continues
  • > 105-≤ 110%: 60 mins
  • > 110-≤ 125%: 10 mins
  • > 125-≤ 150%: 1 min
  • > 150%: 1 sec

Display

  • 5” color touch screen

Standard

  • External battery temperature detection x 1
  • Output dry contact x 4
  • Input dry contact x 2
  • Parallel port x 2
  • USB Port x 1
  • RS232 Port x 1
  • REPO Port x 1
  • Mini Slot x 2

Safety

  • CE
  • RCM (IEC62040-1, IEC62040-2 Class C2)

AC-AC

  • > 96% (Peak efficiency)

ECO Mode

  • 99%

Nominal Voltage

  • ± 240 Vdc (default, ± 180 Vdc – ± 276 Vdc configurable)

Charge Voltage

  • ± 272 Vdc (adjustable from 204 V to 312 V)

Maximum Inbuilt Charger Current

  • 15 A

Discharge Time

  • HPH-20K/B/B-N: 20 mins
  • HPH-30K/B/B-N: 14 mins
  • HPH-40K/B/B-N: 9.5 mins

Operating Temperature

  • 0~40°C

Relative Humidity

  • 0-95% (non-condensing)

Audible Noise (at one meter)

  • HPH-20K/B/B-N: < 50 dBA
  • HPH-30K/B/B-N: < 56 dBA
  • HPH-40K/B/B-N: < 56 dBA

IP Protection

  • IP20 (Standard), IP42 (Optional for long backup model)

Parallel Redundancy and Expansion

  • Up to 4 units

Battery Start

  • Yes

Dimensions (W x D x H) 

  • 240 x 630 x 650 mm

Weight

  • HPH-20K: 44 kg
  • HPH-30K/40K: 50 kg

Dimensions (W x D x H) 

  • 410 x 780 x 1200 mm

Weight (B: with batt.)

  • HPH-20KB: 334 kg
  • HPH-30KB/40KB: 340 kg

Weight (B-N: without batt.)

  • HPH-20KB-N: 94 kg
  • HPH-30KB-N/40KB-N: 100 kg
  • Battery temperature compensation cable
  • Dust filter
  • IP42 kit for long backup model
  • EPO button kit
  • SNMP IPv6 card
  • Modbus card
  • Relay I/O card