DPS Series 300-1200 kVA

Features and Benefits

Overview

Delta’s superior Ultron DPS series 300-1200 kVA UPS supports unity output power factor to deliver up to 10 MW power capacity to meet the demands for large data centers and colocations that require higher power capacity. The Ultron DPS series guarantees the highest level of system reliability and resiliency by supporting self-detection of key components with pre-warning function, multilayered redundancy design, and complete power rating coverage. Moreover, the DPS series supports advanced manageability. Key environment parameters, and event analysis can all be monitored via local 10″ LCD monitor and remotely. Along with optional battery management software, the DPS series enables users to achieve predictive maintenance and minimize system downtime, while lowering the total cost of ownership (TCO).

Specifications

Model

DPS-300K / DPS-400K / DPS-500K / DPS-600K
DPS-800K / DPS-1000K / DPS-1200K

DPS-300K

  • 300 kVA / 300 kW

DPS-400K

  • 400 kVA / 400 kW

DPS-500K

  • 500 kVA / 500 kW

DPS-600K

  • 600 kVA / 600 kW

DPS-800K

  • 800 kVA / 800 kW

DPS-1000K

  • 1000 kVA / 1000 kW

DPS-1200K

  • 1200 kVA / 1200 kW

Nominal Voltage

  • 220/380 Vac
  • 230/400 Vac
  • 240/415 Vac (3-phase, 4-wire + G)

Voltage Range

  • 176/304~276/478 Vac (full load)

Current Harmonic Distortion

  • < 3% (with Full Linear Load); < 5% (with Full Non-linear Load)

Power Factor

  • > 0.99

Frequency Range

  • 40~70 Hz

Voltage

  • 220/380 Vac
  • 230/400 Vac
  • 240/415 Vac (3-phase, 4-wire + G)

Voltage Harmonic Distortion

  • < 1.5% (Linear Load)
  • < 5% (Non-linear Load)

Voltage Regulation

  • ± 1% (static)
  • ± 5% (dynamic)

Output Power Factor

  • 1

Frequency 

  • 50/60 Hz (Auto-Selectable)

Overload Capability

  • ≤ 125%: 10 min
  • ≤ 150%: 1 min
  • > 150%: 1 se

Display

  • 10” Color Touch Panel

Standard

  • RS232
  • Parallel port
  • USB
  • Modbus RS485
  • Input dry contact
  • Output dry contact
  • SNMP card inbuilt in touch screen

Optional

  • Relay I/O card
  • Battery cabinet temperature sensor cable

Safety

  • CE

AC-AC

  • Up to 96.5%

ECO Mode

  • 99%

Type

  • VRLA
  • LiB

Charge Current

  • DPS-300K: 90 A
  • DPS-400K: 120 A
  • DPS-500K: 150 A
  • DPS-600K: 180 A
  • DPS-800K: 240 A
  • DPS-1000K: 300 A
  • DPS-1200K: 360 A

Battery Quantity: 30~46 pcs

Operating Temperature

  • 0~40°C

Relative Humidity

  • 0-95% (non-condensing)

IP Protection

  • IP20

Parallel Redundancy and Expansion

  • Maximum 8 units

Emergency Power Off

  • Remote and local

Dimensions (W x D x H) 

  • DPS-300K: 600* x 900 x 2000 mm
  • DPS-400K/500K/600K: 1200* x 900 x 2000 mm
  • DPS-800K: 1800 x 900 x 2000 mm
  • DPS-1000K/1200K: 2450 x 900 x 2000 mm

Weight

  • DPS-300K: 515 kg
  • DPS-400K: 700 kg
  • DPS-500K: 811 kg
  • DPS-600K: 970 kg
  • DPS-800K: 1270 kg
  • DPS-1000K: 1850 kg
  • DPS-1200K: 2000 kg