DPM Gen2 Series 300-2100 kVA

Features and Benefits

Overview

Selected by leading global cloud providers, Delta’s DPM Gen2 introduces advanced features for enhanced efficiency and reliability. This includes OPEX savings with up to 97.5% AC-AC efficiency and improved grid stability. Synchronized Multiple Bus (SMB) and parallel scalability ensures flawless reliability, making it the ideal solution for fortified hyperscale data centers.

Specifications

Model

DPM-300K/ DPM-600K/ DPM-900K / DPM-1200K / DPM-1500K / DPM-1800K / DPM-2100K

DPM-300K

  • 300 kVA / 300 kW

DPM-600K

  • 600 kVA / 600 kW

DPM-900K

  • 900 kVA / 900 kW

DPM-1200K

  • 1200 kVA / 1200 kW

DPM-1500K

  • 1500 kVA / 1500 kW

DPM-1800K

  • 1800 kVA / 1800 kW

DPM-2100K

  • 2100 kVA / 2100 kW

Parallel Configuration

  • Up to 8 units

Nominal Voltage

  • 480 Vac, 3P3W+PE

Voltage Range

  • 408-552 Vac (100% load)

Frequency Range

  • 40-70 Hz

Total Harmonic Distortion (THDi)

  • < 3% (100% resistive load)

Power Factor

  • > 0.99 (100% load)

Short Circuit Withstand Rating

  • DPM-300-900K: 65 kA
  • DPM-1200-2100K: 100 kA

Connection

  • Single or dual feed

Nominal Voltage

  • 480 Vac, 3P3W+PE

Voltage Regulation

  • ±1% (static)

Frequency 

  • 50/60 ± 0.05 Hz

Total Harmonic Distortion (THDv)

  • < 1% (linear load)

Power Factor

  • 1

Overload Capability

  • < 110%: continues, 110-125%: 10 mins, 126-150%: 1 min, > 150%: 1 sec

Current Crest Ratio

  • 3:1

Online Mode

  • Up to 97.5%

Clean Mode (VI)

  • Up to 99.2%

Battery Type 

  • VRLA
  • Vented lead-acid
  • Lithium-ion
  • Ni-Zinc

Nominal Voltage

  • 480 Vdc

Quantity

  • 34-35
  • 36-46 pcs (VRLA 12 V)

Charge Current

  • DPM-300K: 125 A
  • DPM-600K: 250 A
  • DPM-900K: 375 A
  • DPM-1200K: 500 A
  • DPM-1500K: 625 A
  • DPM-1800K: 750 A
  • DPM-2100K: 875 A

 

Protection Battery shunt trip x1, Battery temperature detection x4, Battery breaker status dry contact x1

 

Display

  • 10-inch color touchscreen

Port

  • Smart slot x2, Modbus (RS-485) port x1, REPO port x1, Input dry contact x6, Output dry contact x6, Synchronized Multiple Bus (SMB) x2, Breaker status detection x4, EMS/Console port x1, Ethernet x1

Remote Emergency Power Off (REPO)

  • Optional

Protocols

  • SNMP
  • Modbus RTU
  • Modbus TCP/IP
  • HTTP(S)
  • SNTP
  • SMTP
  • BOOTP
  • DHCP

Dimensions (W x D x H) 

  • DPM-300K: 1030 x 990 x 2000 mm
  • DPM-1200K: 3070 x 990 x 2000 mm
  • DPM-1500K:3400 x 990 x 2000 mm

Net Weight

  • DPM-300K: 675.5 kg
  • DPM-1200K: 2,408 kg
  • DPM-1500K: 2,779 kg

Operating Temperature

  • 0~40℃ 

Humidity

  • 0-95% (non-condensing)

Altitude

  • 0-2,000 m (derating 1%/100m from 1,001-2,000 m)

Storage Temperature

  • -25 to 70 °C

Ingress Protection

  • IP20

Safety 

  • UL1778

EMC

  • FCC Class A

Performance

  • IEC 62040-3

Sustainability

  • RoHS
  • REACH
  • Energy Star

Standard

  • Advance Power Walk-in for Generator
  • Backfeed Protection with Contactor
  • Burn-in Test without Load Bank
  • Cold Start Function
  • Synchronized Multiple Bus (SMB)
  • Battery Shunt Trip
  • Auxiliary Power 48 Vdc for Shunt Trip

Optional

  • Advance Failure Prediction
  • Grid Interactive
  • Software Integration with Delta Lithium Battery BMS
  • DC Battery Ground Fault Detector
  • Integrated Battery Switch Cabinet
  • IR Scan Window