DPM Gen2 Series 250-1750 kVA

Features and Benefits

Overview

Selected by leading global cloud providers, Delta’s DPM Gen2 introduces advanced features for enhanced efficiency and reliability. This includes OPEX savings with up to 97.3% AC-AC efficiency and improved grid stability. Synchronized Multiple Bus (SMB) and parallel scalability ensures flawless reliability, making it the ideal solution for fortified hyperscale data centers.

Specifications

Model

DPM-250K / DPM-500K/ DPM-750K / DPM-1000K / DPM-1250K / DPM-1500K/ DPM-1750K

DPM-250K

  • 250 kVA / 250 kW

DPM-500K

  • 500 kVA / 500 kW

DPM-750K

  • 750 kVA / 750 kW

DPM-1000K

  • 1000 kVA / 1000 kW

DPM-1250K

  • 1250 kVA / 1250 kW

DPM-1500K

  • 1500 kVA / 1500 kW

DPM-1750K

  • 1750 kVA / 1750 kW

Parallel Configuration

  • Up to 8 units

Nominal Voltage

  • 380/ 400/ 415 Vac, 3P3W+PE or 3P4W+PE

Voltage Range

  • 323-477 Vac (100% load)

Frequency Range

  • 40-70 Hz

Total Harmonic Distortion (THDi)

  • < 3% (100% resistive load)

Power Factor

  • > 0.99 (100% load)

Short Circuit Withstand Rating

  • DPM-250-750K: 65 kA
  • DPM-1000-1750K: 100 kA

Connection

  • Single or dual feed

Nominal Voltage

  • 380/ 400/ 415 Vac, 3P3W+PE or 3P4W+PE

Voltage Regulation

  • ±1% (static)

Frequency 

  • 50/60 ± 0.05 Hz

Total Harmonic Distortion (THDv)

  • < 1% (linear load)

Power Factor

  • 1

Overload Capability

  • < 110%: continues, 110-125%: 10 mins, 126-150%: 1 min, > 150%: 1 sec

Current Crest Ratio

  • 3:1

Online Mode

  • Up to 97.3%

Clean Mode (VI)

  • Up to 99%

Battery Type 

  • VRLA
  • Vented lead-acid
  • Lithium-ion
  • Ni-Zinc

Nominal Voltage

  • 480 Vdc

Quantity

  • 34-35
  • 36-46 pcs (VRLA 12 V)

Charge Current

  • DPM-250K: 125 A
  • DPM-500K: 250 A
  • DPM-750K: 375 A
  • DPM-1000K: 500 A
  • DPM-1250K: 625 A
  • DPM-1500K: 750 A
  • DPM-1750K: 875 A

Protection Design: Battery shunt trip x1, Battery temperature detection x4, Battery breaker status dry contact x1

Display

  • 10-inch color touchscreen

Port

  • Smart slot x2, Modbus (RS-485) port x1, REPO port x1, Input dry contact x6, Output dry contact x6, Synchronized Multiple Bus (SMB) x2, Breaker status detection x4, EMS/Console port x1, Ethernet x1

Remote Emergency Power Off (REPO)

  • Optional

Protocols

  • SNMP
  • Modbus RTU
  • Modbus TCP/IP
  • HTTP(S)
  • SNTP
  • SMTP
  • BOOTP
  • DHCP

Dimensions (W x D x H) 

  • DPM-250K: 1030 x 990 x 2000 mm
  • DPM-1000K: 3070 x 990 x 2000 mm
  • DPM-1250K:3400 x 990 x 2000 mm

Net Weight

  • DPM-250K: 676 kg
  • DPM-1000K: 2,408 kg
  • DPM-1250K: 2,779 kg

Operating Temperature

  • 0~40℃ 

Humidity

  • 0-95% (non-condensing)

Altitude

  • 0-2,000 m (derating 1%/100m from 1,001-2,000 m)

Storage Temperature

  • -25 to 70 °C

Ingress Protection

  • IP20

Safety 

  • IEC 62040-1
  • CE

EMC

  • IEC 62040-2

Performance

  • IEC 62040-3

Sustainability

  • RoHS
  • REACH
  • Energy Star
  • Standard
    Advance Power Walk-in for Generator
    Backfeed Protection with Contactor
    Burn-in Test without Load Bank
    Cold Start Function
    Synchronized Multiple Bus (SMB)
    Frequency Conversion
    Battery Shunt Trip
    Auxiliary Power 48 Vdc for Shunt Trip
  • Optional
    Advance Failure Prediction
    Grid Interactive
    Software Integration with Delta Lithium Battery BMS
    DC Battery Ground Fault Detector
    Integrated Battery Switch Cabinet
    IR Scan Window